Thermosetting enclosure 840x400x250mm IP44 for compensator 10/15/20 kVar





Details
| ID | 1007020 |
| Condition | Nowy |
Product description
1. General Information
Device Name:
Thermosetting enclosure with ventilation and heating.
Application:
Maintaining appropriate temperature conditions inside the enclosure through automatic heating and ventilation.
Power Supply Voltage:
230V AC / 50 Hz
2. List of Components
- Thermosetting enclosure 840x660x320 mm IP44 SSTN 66x84
- 60W semiconductor heater for DIN rail DN-151S-G060W
- Overcurrent switch 1P B 6A 6kA xPole Home HN-B6/1 (194818)
- 2-conductor bus connector 16/25 mm² blue EURO 43403BL
- Protective bus connector 16 mm² green-yellow ZSO1-16.0 (14603319)
- Double thermostat (heating/cooling) TBGZ41 (86.41)
- Fan with filter WEF10 (86.207)
- Installation wires 1.5 mm² (L, N, PE)
3. Operation Description
The system implements automatic temperature control inside the cabinet:
- Heater activates when the temperature drops below 10°C
- Fan activates when the temperature exceeds 40°C
- Control is managed through a double thermostat
Power is supplied from the 230V AC network through the overcurrent switch.
4. Operation Diagram (Connection Description)
- Phase power L is routed through the overcurrent switch
- From the switch:
- to the thermostat input
- Thermostat:
- contacts 11–12 → heater control
- contacts 23–24 → fan control
- Neutral wire (N):
- split by connector
- common for heater and fan
- Protective wire (PE):
- connected to heater
- then to protective connector (PE)
5. Safety Features
- Overcurrent switch B6A
- Protective grounding (PE)
- Enclosure protection class IP44
6. Operating Conditions
- Ambient temperature: according to the components used
- Installation: indoor / outdoor (in accordance with IP44)
- Operating position: vertical
7. User Instructions
- Connect the device to the 230V AC installation.
- Check the correctness of the connection of the wires L, N, PE.
- Do not obstruct ventilation openings.
- Do not interfere with the electrical system during operation.
- In case of damage, disconnect the power supply.
8. Maintenance
- Periodic inspection of electrical connections
- Cleaning of the fan filter
- Checking the operation of the thermostat
9. Final Remarks
A set of components in a technical enclosure, intended for operation as part of an electrical installation.
The product is not a final product and requires connection of power wires.
Installation and connection should be performed by a person with appropriate qualifications.
Attributes